Voltage Drop Calculator

Checks the voltage drop for a specific wire gauge and run, and flags whether it's within NEC-recommended limits.

Advertisement
Distance from source to load, one direction.
Voltage at load
Conductor ampacity
Looking for help?

Get free quotes from vetted local electricians for panel upgrades, rewiring, and installs.

Get free quotes →

We may earn a commission if you hire through this link, at no cost to you.

Advertisement

Single-phase vs three-phase, at a glance

Single-phaseThree-phase
Formula multiplier2√3 (≈1.732)
Drop for identical load/distance/gaugeBaseline~13.4% less
Typical useResidential branch circuitsCommercial/industrial distribution, larger motors

If you're not sure which one applies to your panel, the single-phase vs three-phase wiring guide covers how to tell — most single-family homes are single-phase.

How to use this calculator

Pick the wire gauge already installed (or planned) for the run, the conductor material, the load current, the source voltage, the one-way distance, and whether it's a single-phase or three-phase circuit. The calculator returns the actual voltage drop in both volts and percent, and flags it against the NEC-recommended limits — 3% for a branch circuit on its own, 5% for the combined feeder-plus-branch total.

What voltage drop is and why it matters

Every conductor has some resistance, and current flowing through that resistance loses a small amount of voltage over distance — the longer the run and the higher the current, the more voltage the load actually receives falls short of what the source is putting out. A little drop is normal and code-legal. Too much drop means motors run hotter and less efficiently, electronics can misbehave, and lighting can visibly dim or flicker under load. The NEC doesn't hard-mandate a specific drop percentage as a safety violation the way it does ampacity, but 3%/5% is the long-standing recommended design target, and most inspectors and manufacturers treat it as the practical ceiling.

Worked example

Take a 20A load on 10 AWG copper, 240V single-phase, but this time run 150 feet one-way instead of a short run — long enough that even a properly-ampacity-rated wire starts to matter for voltage drop:

Voltage drop7.46V
Percent drop3.11%
Voltage at load232.5V (of 240V source)
ResultJust over the 3% branch-circuit target — a real-world case where ampacity alone (10 AWG is rated for far more than 20A) would miss the problem

This is the exact case where a wire that's "safe" by the ampacity table can still be the wrong choice for the run — the fix here would be stepping up to 8 AWG, or shortening the run if that's an option.

Frequently asked questions

What's the formula for voltage drop?

For single-phase: VD = (2 × K × I × D) / CM. For three-phase: VD = (1.732 × K × I × D) / CM. Where K is the conductor's resistivity constant (12.9 for copper, 21.2 for aluminum), I is current in amps, D is one-way distance in feet, and CM is the conductor's circular-mil area. Percent drop is just VD / source voltage × 100. This is the same formula the calculator above runs — the worked example shows it applied to real numbers.

What's an acceptable voltage drop percentage?

3% or less for a branch circuit on its own is the standard recommended target; 5% is the ceiling for a branch circuit combined with its feeder. Above that, expect real-world symptoms — dimming, motor inefficiency, or electronics behaving oddly under load — even if the wire is otherwise sized correctly for ampacity.

How is three-phase voltage drop different from single-phase?

Three-phase voltage drop is lower than single-phase for the same wire, current, and distance — the three-phase formula uses a √3 (≈1.732) multiplier instead of the single-phase 2, which works out to roughly 13.4% less drop for identical conditions. That's one reason three-phase distribution is preferred for longer industrial and commercial runs.

Does a longer wire run always mean more voltage drop?

Yes, drop scales linearly with one-way distance in the formula above — double the distance and, all else equal, you double the voltage drop. This is exactly why a wire gauge that's fine for a short run can fail the drop target at 150 feet, as in the worked example, even though its ampacity rating never changes.

Based on NEC Chapter 9 Table 8 (circular mils) and Table 310.16 (75°C ampacity, ≤3 current-carrying conductors). Reference only — verify against the current NEC and local code, and consult a licensed electrician before installing.