NEC Wire Size Chart: Complete Ampacity Reference

Reference guide · NEC Chapter 9 Table 8 and Table 310.16

Every AWG wire size has a maximum current it can safely carry — its ampacity — set by NEC Table 310.16. The table below is the 75°C column, which covers the most common building-wire insulation types (THHN, THWN-2) for up to three current-carrying conductors in a raceway or cable. It's the reference this site's calculators are built on.

AWGCircular milsCopper (75°C)Aluminum (75°C)
144,11020A— (not rated)
126,53025A20A
1010,38035A30A
816,51050A40A
626,24065A50A
441,74085A65A
352,620100A75A
266,360115A90A
183,690130A100A
1/0105,600150A120A
2/0133,100175A135A
3/0167,800200A155A
4/0211,600230A180A
250 kcmil250,000255A205A
300 kcmil300,000285A230A
350 kcmil350,000310A250A
400 kcmil400,000335A270A
500 kcmil500,000380A310A

Why this is the 75°C column specifically

Table 310.16 actually has three temperature columns — 60°C, 75°C, and 90°C — corresponding to different insulation ratings. 75°C (THHN/THWN-2 in wet locations, or most general building wire in practice) is the one most calculators and most residential/commercial branch-circuit work reference. The 90°C column allows higher ampacity for the same wire, but the terminals it connects to (breakers, lugs) are very often only rated for 60°C or 75°C — so the equipment, not the wire, usually ends up being the limiting factor. Don't assume you can use the 90°C ampacity just because the wire insulation supports it.

When this table alone isn't enough

This is the base ampacity table — several NEC-required adjustments can lower the usable ampacity below what's listed here, and none of them are captured by AWG size alone:

None of the tools on this site apply these adjustment factors automatically — they work from the base table. For anything beyond a straightforward, short, well-ventilated run, that's exactly the kind of judgment call worth getting a licensed electrician to confirm.