NEC Wire Size Chart: Complete Ampacity Reference
Every AWG wire size has a maximum current it can safely carry — its ampacity — set by NEC Table 310.16. The table below is the 75°C column, which covers the most common building-wire insulation types (THHN, THWN-2) for up to three current-carrying conductors in a raceway or cable. It's the reference this site's calculators are built on.
| AWG | Circular mils | Copper (75°C) | Aluminum (75°C) |
|---|---|---|---|
| 14 | 4,110 | 20A | — (not rated) |
| 12 | 6,530 | 25A | 20A |
| 10 | 10,380 | 35A | 30A |
| 8 | 16,510 | 50A | 40A |
| 6 | 26,240 | 65A | 50A |
| 4 | 41,740 | 85A | 65A |
| 3 | 52,620 | 100A | 75A |
| 2 | 66,360 | 115A | 90A |
| 1 | 83,690 | 130A | 100A |
| 1/0 | 105,600 | 150A | 120A |
| 2/0 | 133,100 | 175A | 135A |
| 3/0 | 167,800 | 200A | 155A |
| 4/0 | 211,600 | 230A | 180A |
| 250 kcmil | 250,000 | 255A | 205A |
| 300 kcmil | 300,000 | 285A | 230A |
| 350 kcmil | 350,000 | 310A | 250A |
| 400 kcmil | 400,000 | 335A | 270A |
| 500 kcmil | 500,000 | 380A | 310A |
Why this is the 75°C column specifically
Table 310.16 actually has three temperature columns — 60°C, 75°C, and 90°C — corresponding to different insulation ratings. 75°C (THHN/THWN-2 in wet locations, or most general building wire in practice) is the one most calculators and most residential/commercial branch-circuit work reference. The 90°C column allows higher ampacity for the same wire, but the terminals it connects to (breakers, lugs) are very often only rated for 60°C or 75°C — so the equipment, not the wire, usually ends up being the limiting factor. Don't assume you can use the 90°C ampacity just because the wire insulation supports it.
When this table alone isn't enough
This is the base ampacity table — several NEC-required adjustments can lower the usable ampacity below what's listed here, and none of them are captured by AWG size alone:
- More than 3 current-carrying conductors in a raceway requires a derating factor (NEC 310.15(C)(1)).
- Ambient temperature above 30°C (86°F) — attics, rooftops, hot climates — also requires derating.
- Continuous loads (running 3+ hours, like most HVAC or lighting) require sizing the circuit at 125% of the load per NEC 210.19(A).
None of the tools on this site apply these adjustment factors automatically — they work from the base table. For anything beyond a straightforward, short, well-ventilated run, that's exactly the kind of judgment call worth getting a licensed electrician to confirm.
Reference only — always verify against the current NEC edition and local amendments, and consult a licensed electrician for anything beyond a simple, low-risk run.